Description
Pre-filters are the initial line of defense in an air purification system. They are the first stage of filtration, designed to capture larger particles and prevent them from entering the main filtration system. These particles can include dust, hair, pet dander, pollen, and other visible debris commonly found in indoor environments. It can effectively filter harmful substances in the air to ensure your health. We pay attention to every detail, carefully designing and manufacturing the filter wool to ensure that it is tightly structured, not easy to deform, and provides stable and reliable filtration effect.Filter cotton is suitable for home, office, car and other occasions, can effectively purify the air, let you breathe fresh and healthy air environment.
Our filter cotton adopts simple design, which is easy and quick to install, and also very simple to clean, only need to gently tap or rinse with water to restore the filtration effect, saving time and labor.
| Type | Thickness(mm) | Test Air Velocity (m/s) | Rated Air Flow(m3/h) | Average arrestance (EN779) | Initial Resistance(Pa) | Final Resistance (Pa ) | Dust Holding Capacity(g/m2) | FiltrationClass |
| HF-10 | 5 | 1.5 | 5400 | 65% | 15 | 250 | 400 | G2 |
| HF-20 | 10 | 1.5 | 5400 | 70% | 18 | 250 | 420 | G2 |
| HF-30 | 15 | 1.5 | 5400 | 80% | 20 | 250 | 520 | G3 |
| HF-40 | 20 | 1.5 | 5400 | 90% | 25 | 250 | 630 | G4 |
| Item | Specification |
|---|---|
| Product Name | White Progressive-Density Pre-Filter Media Roll |
| Product Type | Primary Air Intake Filter Media |
| Model Series | HF |
| Standard Models | HF-10 / HF-20 / HF-30 / HF-40 |
| Filter Material | Synthetic Fiber |
| Filtration Grades | G2 / G3 / G4 |
| Structure | Multilayer Progressive-Density Nonwoven |
| Standard Color | White |
| Thickness Range | 5–20 mm |
| Test Air Velocity | 1.5 m/s |
| Rated Airflow | 5400 m³/h |
| Initial Resistance | 15–25 Pa |
| Recommended Final Resistance | 250 Pa |
| Dust-Holding Capacity | 400–630 g/m² |
| Supply Form | Roll / Cut Pad / Framed Pad |
| Main Function | Coarse Particle Capture and HEPA Pre-Filtration |
| OEM / ODM | Available |
| HVAC & Air Intake Systems | Spray Booths & Painting Workshops | HEPA Pre-Filtration | Industrial Air Filtration |
|---|---|---|---|
| Used as primary filtration media in AHUs, central air-conditioning systems, fresh-air units, fan coil systems, and return-air inlets. | Captures dust and fine contamination at spray booth air inlets, painting equipment, workshops, and baking installations. | Installed upstream of medium- and high-efficiency filters to reduce dust loading and extend HEPA filter service life. | Suitable for factories, clean-air equipment, ventilation units, air purifiers, and general dust-removal systems. |
| Customization Available | Quality Inspection |
|---|---|
| • Custom roll width and roll length • 5 / 10 / 15 / 20 mm or custom thickness • G2 / G3 / G4 filtration configurations • Custom fiber density and basis weight • Support mesh and adhesive-treatment options • Roll, cut-pad, or framed-pad supply • Washable or disposable configurations • OEM labels, branding, samples, and export packaging |
• Roll width, length, and thickness inspection • Fiber density and progressive-structure verification • Support mesh and adhesive-treatment inspection • Surface uniformity and fiber-shedding check • Airflow and initial-resistance testing • Average arrestance testing upon request • Dust-holding capacity verification • Final appearance and packaging inspection |